Main features
• Damper blades in tightness class 4
• Supplied with mounting shelf for actuator control
• Actuators are available in several alternatives, see product sheet for details
• Can be used as a shut-off damper (pressure class A, up to 300 Pa)
• Prepared for 50 mm external insulation
Description
• SPT is a damper for installation in circular ducts. The product comes with a mounting shelf that fits most conventional actuators.
• The damper can be ordered with a mechanical handle for manual operation or alternatively fitted with an actuator. Please see Options and aceessories or download the product sheet for current actuator options.
• The product can be used for commissioning purposes, or as regulating or shut-off damper.
(pressure class A, up to 300 Pa).
• The damper is prepared for 50 mm external insulation.
* The product is displayed with separately sold accessories.
Materialvalg og overfladebehandlinger:
• Galvaniseret stålplade (standard)
• Pulverlakeret udførelse.
Størrelser (mm):
Ø100 / Ø125 / Ø160 / Ø200 / Ø250 / Ø315 / Ø400 / Ø500 / Ø630
Driftsalternativer:
• Spjældmotorer findes i flere alternativer, se produktblad for mere information.
• Manuel betjening med mekanisk håndtag.
Andet tilbehør
• PTS – Regulatorhylde
• AX – Spjæld akselforlængelse
• SRS – Forlænget motorhylde
• Product in standard version comes with damper housing and blade of galvanized sheet steel but can also be ordered in painted versions.
• The products meet corrosivity class C3 and pressure class A with housing in density class C.
• The product is fitted with a damper blade in tightness class 4 unless otherwise specified.
• The product is fitted with gaskets of EPDM rubber.
• Circular products have nipple dimensions with rubber gaskets and are mounted with a sliding muff (female slide-in coupling).
• Circular products can be installed in any position and require no maintenance.
• The product can be delivered for manual operation, fitted with a mechanical handle, but is optionally available in motorized version with several actuator types available (specified when ordering).
• Motorized products are not intended for use in cold or aggressive environments.
• Motorized products may only be installed by authorized personnel. All rules and regulations issued by authorities in the country of usage
must be followed during installation.
• All wiring must be done with the power supply disconnected.
• When installing, space should be reserved for access to the device's actuators and/or readability of units equipped with a display.
• Please see the products operation and maintenance documentation for detailed information on mounting.
• Please see third party documentation for details on wiring and connection of the selected actuator type depending on model and make.