FreeAir

Main features

• Low-profile design (120 mm) for exposed installation.
• Horizontal air distribution in two directions
• High cooling/heating capacity with low noise levels
• Prepared for connection of control and power
• Adjustable air deflectors for a draught-free indoor climate
• Fold-down front grille for inspection and service
• Supply air volumes from 10 l/s (35 m3/h)
at 50 Pa up to 35 l/s (125 m3/h) at 100 Pa

Description

• FreeAir is a low-profile induction unit for supply air, cooling and heating, adapted for exposed installation.

• Supply air and return air are distributed in the room horizontally in two directions along the suspended ceiling.

• With the supply air flow as the driving pressure, room air is induced through the finned coil, which removes or, where applicable, adds heat.

• The unit's supply air duct has fixed nozzles on each long side.

•The product is also equipped with Airflex, adjustable air deflectors. The  deflectors makes it possible to achieve a draught-free indoor climate.

• The front of the chilled beam is made of perforated sheet metal can be easily folded down for inspection and service.

• The front grille comes with square shaped perforation as standard. Circular perforation is available as a special order.


Configuration options
• Supplied in three duct dimensions: Ø125/160/200
• Water connection side: left / right
• Multiple units can be serially connected for higher efficiency requirements.

Options
• Cladding options are offered through partners, which offwea a wide choice in color and material selection.
• Supply air grilles in two designs: AC and E5.
• Mounting frame for easier installation and maintenance of supply air grilles: RAM.
• Integrated control for stand-alone operation or connectivity to parent BMS.
• Complete selection of connection accessories:
– Setpoint changer.
– Connection hoses (set of 4).
– Control valves for water supply.
– Valve actuators.


• Device housing and duct connection made of hot-dip galvanized sheet steel with EPDM rubber gasket.

• Visible parts: casing, frame and perforated front grille made of sheet steel, powder coated in white RAL standard colour. Other colours are available.

• Coil made of copper tubes with aluminum slats.

• Plastic details of Polyethylene.

• For more information about standard materials and colors, see the separate document Product specification which can be downloaded from our website.


• The following information is only a general overview of the of assembly, installation and adjustment procedure. Always refer to the product's operation and maintenence documention (DU-SE/DV-DK) for detailed installation instructions.

• The unit is mounted in the specified number of suspension points based on the current product length, see the dimensional drawing in the product's operation and maintenence documentation (DU/DV).

• The product is connected to a circular supply air duct. Connection to a straight mounted flexible duct is not recommended.

• Heating and cooling water pipes are installed by a plumbing contractor.

• Ensure that no damage occurs to the cooling/heating coil when tightening valves and connections. To avoid this, always use a suitable wrench as counterweight.

• When installing the beam, space should be reserved for opening the front grille and accessing the device for cleaning, inspection and service.

• The product has fixed nozzles and is delivered for specific air flow at a certain nozzle pressure according to customer requiement (specified at order placement).

• It is possible to have a certain number of nozzles plugged on delivery in order to increase airflow later if necessary.

• The supply air flow is checked by measuring the operating pressure in any nozzle across the nozzle strips. When the prescribed operating pressure has been measured, the specified air flow has been achieved.

• In order to adjust the operating pressure, the product should be preceded by an comissioning damper mounted in the duct before the  unit, e.g. ZMC, but not an iris-type damper.

• When installing the commissioning damper, requirements for the preceding straight section should be taken into account, see the specific damper's documentation for detailed information.

• For calculation of K factors, see tables and calculation formula in the operation and maintenance document (DU/DV) of the beam. For K factors with a commissioning damper, please refer to the documentation of the specific damper to be used.

• When the unit is supplied with control options, the product is delivered internally pre-wired from the factory. See separate documentation depending on the current option regarding wiring, commissioning and operation of control and powering components.


Material options and finishes
• Powder coated finish.

Sizes (mm)
• Supplied in 6 different lengths:
1500/1800/2100/2400/2700/3000
• Duct dimension Ø100

Configuration alternatives
• Version for cooling or cooling and heating.
• Selectable water connection side: same as the air duct or opposite side.
• Available in versions with 1 or 2 water circuits.

Options and accessories
• Integrated control for stand-alone operation or connectivity to parent BMS.
• Complete selection of connection accessories:
– Adjustment damper type ZMC
– Setpoint changer.
– Connection hoses.
– Control valves for water supply.
– Coanda 'cape'
– Valve actuators.